VS65 SERIES MV SOFT STARTER
POWER ELECTRONICS
32
MODBUS COMMUNICATION
5.3.3. General Information Screens
Parameter
Screen
Description
Address
Range
Modbus Range
G0.1 L1
800A 800A 800A
Phase Current L1
40185
0-9999
-
G0.1 L2
800A 800A 800A
Phase Current L2
40186
0-9999
-
G0.1 L3
800A 800A 800A
Phase Current L3
40187
0-9999
-
G0.2V12
6000V 6000V 6000V
Line Voltage L12
-40188
0-999
-
G0.2V23
6000V 6000V 6000V
Line Voltage L23
-40189
0-999
-
G0.2V13
6000V 6000V 6000V
Line Voltage L13
-40190
0-999
-
G0.3
50Hz Cos=0.85
Line Frequency
-40191
0-1
-
G0.4
450kW Pr=99%
Motor Torque
-40193
0-999
-
G0.4
450kW Pr=99%
Motor Power
40194
0-999
-
G0.5
RELE= 0 0 0
Relay Status
-40195
No
-
G.06
EDG= 0 0 0 0 0 F
Digital Input Status
40196
No
-
G.07
ESTADO SOB=0%
Motor Overload
40197
0-100%
100% Overload
Condition
-
EA1=0.00mA = 0%
Analogue Input 1 Status
0-10V
4-20mA
0-20mA
-
EA2=0.00mA = 0%
Analogue Input 2 Status
V ó mA
0-10V
4-20mA
0-20mA
-
SA1=0.00mA = 0%
Analogue Output 1 Status
0-20mA
4-20mA
-
S/W 2.1 H/W 0.2
Hardware and Software Revision
-
-
-
5.3.4. Programming Parameters
Parameter
Screen
Description
Address
Range
Modbus Range
G1.1
1 LOCK PARAM=NO
Soft starter parameters lock
Yes
No
-
G1.2
2 PASSWORD= 0
Programming Password mode
-
OFF,
0000 to 9999
-
G1.2b
3 WRONG P/W=XXXX
Password Recovery
-
0000 a 9999
-
G1.6
6 COMMISSION=YES
Commissioning
40019
Yes
No
0-1
G2.1
1 I STARTER =xxxA
Soft starters Rated Current
40022
7A
17A
30A
45A
...
1600A
1-1600
G2.2
2 I MOTOR=XXX[*]A
Motor Plate Current
40023
1 to 1600
1-1600
G2.3
3 V MOTOR=2
Input Line Voltage
40024
1 to 4
1-4
G2.4
4 P MOTOR =450kW
Motor Power Plate
40025
4 to 999kW
40-9990
G2.5
5. COS PHI M =85%
Motor Phi Cosine
40026
40 to 99%
40-99
G2.6
6 FREQ= 50Hz
Supply Frequency
40027
50Hz
50/60Hz
0-1
G3.1
1 PHASE SEQUEN=2
Phase Sequence at the Soft starters Input
40029
1 to 3
1-3
G3.2
2 OV LOAD=InA
Motor Overload Current
40030
(0.6 to 1.5)·In of
the VS65
120-300
G3.3
3 OV/LOAD T=5
Overload Curve
40031
1 to 10
1-10
G3.4
4 OVL FAC=100%
Starting Overload Factor
40032
100 to 500%
100-500
G3.6
6 UNLOAD=0.0A
Underload Current
40034
(0 to 0.9)·In of VS65
0-180
G3.7
7 UNLOAD T=OFF
Underload Delay
40035
0 to 99s, OFF
0-100
G3.8
8 SHEARPIN=OFF
Shearpin Current
40036
(0.6 to 1.2)·In of
the VS65, OFF
120-240
G3.9
9 ASYM I ENB=Y
Asymmetrical Protection
40037
Y
N
0-1
G3.10
10 UNDER V=5052V
Under Voltage
40038
G3.11
UNDERVOLTAGE
DELAY
Under voltage Delay
40039
0 to 10s, OFF
0-11
G3.12
12 OVERVOLT=6947V
Over voltage
40040
400-460
G3.13
13 O/V DELAY=5s
Over voltage Delay
40041
0 to 10s, OFF