EasyManua.ls Logo

Power Electronics VS65 Series - Configuration Table

Power Electronics VS65 Series
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VS65 SERIES MV SOFT STAR
TER
POWER ELECTRONICS
12
CONFIGURATION TABLE & STANDARD RATINGS
2. CONFIGURATION TABLE & STANDARD
RATINGS
2.1. Configuration table
Example of the selection table module soft starter VS65
CODE: VS6520064CLT
VS65 200 6 4 CL T - -
VS65
Series
Output
current
[1]
Input
voltage
Protection
degree
Configuration Power cable access Fuses Metal-Clad
200 200ª 2 2300V 4 IP41 CL
Fixed line
contactor
-
Bottom input and
output connection
-
No
fuses
-
Without
Metal-Clad
400 400ª 3
3000V
3300V
5
[3]
IP54 CX
Removable
line contactor
T
Top input a
nd
bottom output
connection
F
[3]
With
fuses
M
[3]
With Metal-
Clad
4 4160V
C
[2]
Without line
contactor
U
Top input and
output connection
6
6000V
6600V
8
10000V
11000V
-
Under
request
Notes:
[1] Check the rated current of the motor nameplate to guarantee the compatibility with the selected
soft starter.
[2] In these cases it is required an additional input protection cell.
[3] Consult availability with Power Electronics.

Other manuals for Power Electronics VS65 Series

Related product manuals