POWER ELECTRONICS
VS65 SERIES MV SOFT STARTER
PREVENTIVE MAINTENANCE
45
Inspection site
Inspection
element
Inspection
Period
Inspection method Criterion
Instrument of
measurement
Daily
1 year
2 years
3 years
Control circuit
and protections
Operating
check
Is there any imbalance
between output voltage
phases?
o
Measure voltage between output
terminals U, V and W.
voltage between
phases i.e. lower
than 8V
difference for
400V models.
Digital
multimeter /
RMS voltage
meter.
Display
All
Is the displayed value
correct?
o
o
Visual check.
Check the reading instrument with
an external measurement.
Clean the screen.
Check the
specified values
and the control
values are
equal.
Voltmeter,
amperemeter.
Motor
Insulation
resistance
terminals of output
circuit and ground
terminal)
o
Disconnect the cables U, V and W
and join them together. Check the
resistance between this join and
ground.
More than 5MΩ
Megger type
2500V
All
abnormal vibrations?
Has any unusual smell
been perceived?
o
Audible, sensory and visual check.
Check if damages have been
produced by overheating.
No anomaly.