Emergency
Retract Fitted ?
Emergency Access
Fitted ?
Auto Reset
Enabled
Option 1
E Retract Time Set
Option 2
Push To Operate
Is Curtain Fully Open
Option 3
Repeat Alarm
Delay Alarm Rq’d
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Split Drop Rq’d
Close Wait or
Smoke Curtain
Smoke Curtain
Close Wait
Delay Alarm Time
0 - 30 minutes
Close Warning
0 - 10 minutes
Close Wait (Hold)
0 - 30 minutes
Smoke Curtain Infinite
Hold Time Until
Alarm 2 Activated
Fully
Close Curtain
Curtain Will Remain
Closed After Alarm &
Require Manual Reset
Has Time Expired ?
No
P1000 Alarm
Open Curtain
Open Curtain
Open Curtain
Re-open Curtain
After Alarm
Open Curtain
Alarm 2 Activation Alarm 1 Activation
No
Momentary Push Of
Emergency Retract
Button
Momentary Push Of
Emergency Retract
Button
Push & Hold
Emergency Retract
Button
Push & Hold
Emergency Access
Button
Release Emergency
Retract Button
Release Emergency
Access Button
P1000 Alarm Operation Flowchart