IMPORTANT NOTICE FOR GATE OPERATORS
MANUFACTURED AFTER JANUARY 11TH, 2016
All gate operators manufactured after January 11th, 2016 must have a
monitored input for each direction. In order to satisfy this requirement,
all PowerMaster gate operators with the universal board will have one
monitored input for each direction. The close photo (11) terminal will
function for the close direction and the open photo (10) will function
for the open direction. These terminals will look for, or “monitor”, the
presence of a 10k in-line resistor. If either terminal does not detect the
presence of the monitored device, the unit will function in constant
contact for this direction.
Note: The rst time a monitored device is added to the unit, the board
must “learn” what the monitored device is. To have the board learn the
monitored device, perform the following steps:
1. With the power o, hold both the open and close limit
simultaneously.
2. Power up the unit and release your ngers from the limits. The
unit has now learned the monitored device.
E.g. The operator detects there is a monitored device on the 11 terminal
but not the 10 terminal. The operator will function in momentary
contact to close and constant pressure to open.
Following are the monitored devices acceptable for use with the
GSMCB02:
Any actions taken to circumvent this monitoring are in violation of the
UL325, building code, and local laws.
Device Manufacturer Description
Prime-Guard Miller Edge Monitored Photoeye
Reecti-Guard Miller Edge Retroreective Monitored Photoeye
IRB-MON EMX Monitored Photoeye
IRB-RET EMX Retroreective Monitored Photoeye
The Solution Miller Edge Multiple Safety Devices