EasyManuals Logo

PowerMax 155x Series User Manual

Default Icon
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
THE APPLIANCE WILL NOT:
IGNITE THE BURNER
DELIVER HOT PRODUCE
WATER CENTRAL
HEATING
DOES THE FLOW
SWITCH OPERATE THE
HE. PUMP IE 230V AT
TERMINAL 23 WHEN THE
BURNER IS NOT LIT
IS THE CYLINDER UP TO
THE CORRECT
TEMPERATURE
YES
CHECK THE BLENDER VALVE.
CHECK THE FLOW RATE IS
NOT GREATER THAN 121/MIN
IF THE FLOW IS POOR CHECK
THE INLET STRAINER AND
INCOMING WATER SUPPLY
CHECK THE FLOW SWITCH
RELAY ASSEMBLY, REPLACE IF
FAULTY
IS THE APPLIANCE/
PROGRAMMER/ROOMSTAT CALLING
FOR HEAT IE 230V AT TERMINAL 28
NO
START
NO
CHECK THE BOILER STAT
YES
CHECK THE COLD START STAT
(DOMESTIC PRIORITY STAT) IT WILL
NOT ALLOW CENTRAL HEATING
WHEN THE CYLINDER STORE
TEMPERATURE IS BELOW 65°C
IF OK CHECK PUMP AND
CONNECTIONS AT TERMINAL
25 AND N2
IS ORANGE NEON LIT
NO
IS THERE 230V TO
THE UNIT
YES
CHECK CIRCUITRY TO AND
AROUND NEON. IF CORRECT
REPLACE NEON.
NO
YES
CHECK FOR 230V EITHER
SIDE OF FILTER.
IF FAULTY REPLACE.
CHECK MAINS SUPPLY
LEAD/FUSE. REPLACE AS
NECESSARY.
DOES THE FAN RUN
NO
IS THERE POWER
TO THE FAN
YES
CHECK FAN CAPACITOR
AND WIRING FOR FAULT
CHECK FOR DAMAGE OR
BLOCKAGE TO THE FAN
REPLACE CAPACITOR/
REPLACE FAN
HAS THE LIMIT STAT TRIPPED
TEST FOR AND RECTIFY ANY
OVERHEAT FAULT, I.E.
DEFECTIVE BOILER STAT
YES
CHECK HEAT EXCHANGER PUMP
WORKING AND NOT AIR
LOCKED. REPLACE IF FAULTY.
CHECK BOILER
THERMOSTAT IS CALLING
FOR HEAT.
YES
CHECK CIRCUITRY TO FAN
FROM IGNITION CONTROLLER.
REMOVE IGNITION CONTROLLER
AND CHECK INTERNAL FUSE.
IF FAULTY REPLACE WITH
CORRECT 20mm FUSE,
I.E. 2A HRC
IF FUSE IS OK
REPLACE CONTROLLER.
NO
NO
NO
YES
CHECK IF PROGRAMMER/HEATING
SWITCH IS CALLING FOR HEAT.
CHECK SWITCH + WIRING FOR 230V
BETWEEN SWITCH/PROGRAMMER
AND BOILER STAT.
IS THE RED NEON LIT
SWITCH OFF WAIT 10 SECS
SWITCH ON
YES
NO
DOES SPARK
ELECTRODE SPARK
NO
DOES THE IGNITION
CONTROLLER GENERATE
A SPARK.
REMOVE THE BURNER AND
REPLACE (OR CHECK)
ELECTRODE. THE CORRECT
SPARK GAP IS 3.5/4.0mm
YES
REPLACE ELECTRODE IF FAULTY
(ADJUST ELECTRODE BY
MOVING EARTH POST ONLY).
PLACE THE ELECTRODE END OF
THE HT LEAD ON BURNER. IS A
SPARK TO THE BURNER VISIBLE?
REPLACE IGNITION CONTROLLER
NO
ENSURE THAT H.T. LEAD
IS PROPERLY CONNECTED
AT CONTROLLER AND THAT
THE WHITE EARTH WIRE IS
PUSHED HOME ON THE
ELECTRODE EARTH PLATE
NO
YES
IS GREEN NEON LIT
IS GAS PRESENT AT GAS VALVE
INLET PRESSURE TEST POINT
CHECK GAS IS CONNECTED AND
TURNED ON. CHECK FOR
OBSTRUCTIONS IN GAS LINE.
IS GAS PRESENT AT GAS VALVE
OUTLET PRESSURE TEST POINT
DURING IGNITION ATTEMPT
APPROX 4.5 mbar
CHECK FOR 230V AT
TERMINAL G1
CHECK OVERHEAT STAT AND
WATER LEVEL SWITCH AND
RECTIFY FAULT, E.G. REFILL
SYSTEM.
IF OK CHECK FOR 230V AT PIN
8 (BLACKWIRE) ON THE
IGNITION CONTROLLER
CHECK FOR FAULT AT GAS
VALVE OR AIR SENSE LINE.
CHECK FAN PRESSURE IN AIR
SENSE LINE IS BETWEEN 4.5
AND 5.2 mbar.
CHECK FAN, FLUE WAYS AND
INJECTOR HOUSING FOR
OBSTRUCTION AND RECTIFY.
IF SATISFACTORY CHECK COIL
ON GAS VALVE. REPLACE
COIL/GAS VALVE AS
NECESSARY.
NO
NO
YES
YES
NO
YES
YES
NO
YES
NO
YES
DOES APPLIANCE
REMAIN RUNNING
IF STUTTERING IGNITION IS
OBSERVED, CHECK ELECTRODE
AND CONNECTION AS IN
PREVIOUS COLUMNS.
IF SMOOTH IGNITION IS
OBSERVED BUT BURNER GOES
OUT AFTER APPROXIMATELY
3 SECONDS CHECK IGNITION
CABLE/ELECTRODE. REPLACE
AS NECESSARY.
IF IGNITION CABLE AND
ELECTRODE OK THEN REPLACE
IGNITION CONTROLLER.
NO
CHECK ELECTRODE AS IN
PREVIOUS COLUMNS. CHECK
ELECTRODE GAP DISTANCE
FROM BURNER FACE. IF NOT
APPROX. 13mm RECTIFY.
TURN OFF GAS AND USE
MIRROR TO CHECK FOR
STRAY HT SPARKING.
APPLIANCE
SATISFACTORY
YES
IS BOILER GAS RATE
SATISFACTORY
CHECK FLUE PIPES ARE
NOT BLOCKED
CHECK THAT THE FLUE PIPE
IS CORRECTLY CONNECTED
TO TERMINAL
CHECK THAT THE MAXIMUM
LENGTH OF AIR/FLUE PIPES
AND BENDS HAS NOT
BEEN EXCEEDED
NO
YES
5.0 (155
N
) or 4.0 mbar (140)
4.8.5.5 (155
N
) 3.8.4.4 (140)
CHECK THE BLENDER VALVE.
CHECK THE FLOW RATE IS NOT
GREATER THAN 12 L/MIN (140)
18 L/MIN (155
N
) IF THE FLOW IS
POOR CHECK THE INLET
STRAINER AND INCOMING
WATER SUPPLY
4
4.0mbar(140) or 5.0(155
N
)
3.8 - 4.4(140) 4.8 - 5.5(155
N
)mbar
12
Fault finding chart

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PowerMax 155x Series and is the answer not in the manual?

PowerMax 155x Series Specifications

General IconGeneral
BrandPowerMax
Model155x Series
CategoryBoiler
LanguageEnglish

Related product manuals