5
2. Overview
NOTE: The equipment has been thoroughly checked before shipment. Upon receipt, check the packaging and en-
sure that the contents are undamaged and that no items are discarded. Any damage must be reported to the shipper
and any missing parts must be reported to the supplier immediately. Please keep the original package in a safe
place for future use.
2.2 Packing List
Unpack the package and check the package contents. The shipping package contains:
UPS Shipping Package Optional Extended Battery Cabinet
1. One UPS 1. One Battery Cabinet
2. One User Manual 2. One Battery Cable
3. Mounting Ears 3. Mounting Ears
4. Two Sets of Tower Stands (Feet) 4. Two Sets of Tower Stands (Feet and Extensions)
5. Rail Kit 5. Rail Kit
6. USB Cable
2.1 UPS Devices and Batteries
The following table provides an overview of the various versions of the device:
Sinergy III UPS Model Battery Cabinet Model
ACDEF700-11 E024-12
ACDEF1000-11 E024-12
ACDEF1500-11 E036-12
ACDEF2000-11 E048-12
ACDEF3000-11 E072-12
ACDEF2000-22 E048-12
ACDEF3000-22 E072-12
2.3 Storage
If the UPS is to be stored prior to use, it should be stored in a clean, dry environment and away from temperature
extremes. It is recommended that the equipment be stored in a temperature controlled, moderate humidity environ-
ment. The table below provides the temperature and humidity storage limits:
NOTE: When storing equipment, every 8°C above 25°C reduces the shelf life of the battery by 50%. More
frequent battery charging is required to maintain the batteries in storage at these greater temperatures.
Storage Data
Temperature Limits 32°F to 104°F (0°C to +40°C)
Relative Humidity (Non-Condensing) 0% to 90%