5.0 APP - Application selection
5.1 tAR - Selection of taring type
Possible selections are tLO - 0% taring enable, tHI - 100% taring enable, or dtA - taring disabled.
If tLO is selected, activating the 3 key for more than 2 s or activating the digital input will tare the input signal to
0%.
If tHI is selected, activating 3 for more than 2 s or activating the digital input will tare the input signal to 100%
(max.).
The 2 types of taring can be used for filling or emptying respect ively.
If a 0% (tLO) taring is selected, the analog input will show 0% after taring. If a 100% (tHI) taring is selec ted, the
input will show 100% after taring corresponding to tara + net weight = gross weight.
Taring is either from the digital input or from front.
5.2 dIN - Selection of digital input type
Possible selections are:
PnP = mechanical contact or open collector transistor connected to +24 VDC.
nPn = mechanical contact or open collector transistor connected to gnd.
5.3 SUP - Setting of supply voltage for transducer
Valid selections are 5.0...13 VDC.
5.4 PAS - Setting of password
Key 2. When the password is 040, changes can be made in all menu points. When the password is <> 040,
programming is blocked in all menu points, but access is open for reading the settings. Enter the password by the 3
and 1 keys.
When the password is correct, activate 3 and 1 simultaneously. Valid selections are 0...999.
5.5 Frq - Selection of common mode frequency suppression
Possible selections are 50 or 60 Hz.