16 4116V105-UK
Readout at hardware error
Error search Readout Cause
Test of internal CJC sensor CJ.ER CJC sensor defect or temperature outside range
Checksum test of the configuration in FLASH FL.CO Error in FLASH
Check measurement of analog output current AO.ER
1) No load on the current output
(only S4...20 / S20...4 mA)
Communications test 45xx / 4116 NO.CO Connection error
Check that input signal matches input
configuration
IN.ER 1) Error levels on input
Check that saved configuration in 45xx matches
device
TY.ER Configuration is not 4116
!
All error indications in the display flash once per second. The help text explains the error. If the error is a
sensor error, the display backlight flashes as well - this is acknowledged (stopped) by pushing the 3
button.
1) The error is reset by switching off and then switching on the supply voltage to the device.