27
Ø
Automatic Restart
:
n
Enable
: Once "Enable" is set, no matter what the UPS state was before, it will restart to Online
mode automatically after the utility recovers.
n
Disable
: Once "Disable" is set, the UPS will operate normally. If the UPS is turned off due to low
battery, it will still restart to online mode after the utility recovers. If the UPS is manually shut
down and the utility recovers, it switches to standby mode or bypass mode depending on the UPS
configuration.
Ø
Shutdown Delay
: The UPS will shut down within minutes of setup. The countdown will begin after
confirming the pop-up screen.
Ø
Recover Delay
: The UPS will automatically restart within minutes of setup after the UPS is turned off.
Ø
New Password
: Set a new password to enter the "èADVANCE User" menu page.
Ø
Built-in User Password:
n
YES
: Once "YES" is set, the User's password will restore the default setting value.
n
NO : After "NO" is set, UPS will cancel this operation.
Ø
Battery Lock
: Currently, this setting is not available.
UPS SELFTEST
This function is effective only when the UPS type setting is "HV". Therefore, please remove all loads and
utilities first before performing this function. Then, please change the UPS type to "HV". For detailed
operation, please check the "System Parameters" menu below
Advanceè Maintainer directory
After changing the UPS type to "HV", you must restart the UPS. After the UPS restarts, please enter the
Advanced screen and enter the Maintenance password. This will display the "UPS SELFTEST" option on the
screen. On the screen, all tested items are displayed "unknown". Just click the "UPS SELFTEST" button, the
UPS will start the self-test. If the UPS is normal, it will display "Normal" in all columns. Otherwise, "Unknown"
will be displayed in the column.
After the UPS self-test passes, the screen will go black automatically. If the UPS self-test is abnormal, the
UPS will stop at the abnormal screen. At this time, the maintenance personnel must repair the UPS
according to the self-test instructions. Please check your local dealer for self-test instructions.

Other manuals for PROLiNK MASTER II Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PROLiNK MASTER II Series and is the answer not in the manual?

PROLiNK MASTER II Series Specifications

General IconGeneral
BrandPROLiNK
ModelMASTER II Series
CategoryUPS
LanguageEnglish

Related product manuals