Prolon T1100 - Menu Guide; 4.4) Heat Int; 5.1) Heat SP Min; 6.1) Heat Offset

Prolon T1100
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section Description Min Max Default Units
4.4) Heat Int Defines the amount of time required for the
heating integral component of the demand
to equalize the proportional component.
Setting this value to zero removes the
cooling integral component of the demand.
0 120 15 min
5 30 19 °C5.1) Heat SP
Min
During occupied mode, the thermostat will
use this value as a low limit for the heating
setpoint.
41 86 66.2 °F
6 44.5 25 °C5.2) Heat SP
Max
During occupied mode, the thermostat will
use this value as a high limit for the heating
setpoint.
42.8 112.1 77 °F
5.5 44 20 °C5.3) Cool SP Min During occupied mode, the thermostat will
use this value as a low limit for the cooling
setpoint.
41.9 111.2 68 °F
6.5 45 26 °C5.4) Cool SP
Max
During occupied mode, the thermostat will
use this value as a high limit for the cooling
setpoint.
43.7 113 78.8 °F
0 20 3 °C6.1) Heat Offset During unoccupied mode, the active heating
setpoint is decreased by this amount.
0 36 5.4 °F
0 20 5 °C6.2) Cool Offset During unoccupied mode, the active cooling
setpoint is increased by this amount.
0 36 9 °F
5 30 15 °C6.3) Heat SP
Lim
During unoccupied mode, the thermostat
will use this value as a low limit for the
heating setpoint.
41 86 59 °F
5.5 45 30 °C6.4) Cool SP Lim During unoccupied mode, the thermostat
will use this value as a high limit for the
cooling setpoint.
41.9 113 86 °F
6.5) Unocc
Overr Time
The time spent in occupied mode once the
thermostat is manually overridden from
unoccupied mode.
0 720 120 min
12