EasyManua.ls Logo

Protectowire 2000 FireSystem - );)*#)&*%$)$)**%$$%&(*%$; Information and Specifications; System Specifications; Notification Appliance Circuits

Protectowire 2000 FireSystem
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
))5B95C9B55D53D9?>
5<E75&B513D9?>?>DB?<&1>5<>6?B=1D9?>1>4)@5396931D9?>C
The FS2000 Series of multiple zone fire protection panels is the latest in fire protection from The Protectowire Company, Inc. The
standard model provides, as a minimum, 2 (Class A or B) initiating device circuits and the following standard features:
- Expandable (in multiples of two zones) - Ground Fault Detection (not applicable to all systems)
- Two Supervised Notification
Appliance Circuits - Alarm Lock-in until Reset
- On Board Audible Indicator Silencing - On Board System Reset Button
- Lamp and System Trouble Circuit Test - Dry Alarm and Trouble Contacts
- Initiating Device (Detection) Circuit -IDC- ALARM Test
- Monitors up to 5,000 ft. (1,524 meters) of PROTECTOWIRE Linear Heat Detector Cable per circuit
- Any combination of normally open contact devices
- Accommodates up to (30) NS-series #SLR-24, #SIJ-24, #SLR-24H, Detector Identifier - HD-3
Smoke Detectors (per circuit).
- Battery Monitoring, Low or Out of operating specs. (or disconnected)
)ICD5=)@5396931D9?>C
$?D96931D9?>@@<91>359B3E9DC
Note: Circuits do NOT generate a temporal pattern signal. Appliances that can generate a temporal pattern must be employed
when a temporal pattern is required. Reference DS-9066 in this manual for compatible devices.
~ 4~
&B9=1BI&?G5B
120VAC 50/60Hz 1.75 amp maximum ** see below
)E@@?BD54)D1>42I1DD5B95C
24VDC 4.5AH minimum to 60AH maximum * see below
1DD5BI81B75B
27VDC 1.25 Fast charge, 27.6mA Max trickle charge, 12mA (typical)
&B9=1BI)ICD5=&?G5B
24V FWR by T1, 175VA typical. Greater VA rating as required by system
)ICD5=(57E<1D54&?G5B
MB and EB type boards provide 12 & 24VDC regulation. RS type boards
provide24VDC regulation only
?==?><1B=?>D13DC
3 amps @ 30VDC, resistive load, silenceable
?==?>*B?E2<5?>D13DC
1 amp @ 24VDC, resistive load, factory preset as non-silenceable
?==?>)E@5BF9C?BI?>D13DC
1 amp @ 24VDC, resistive load, programable
?EBG9B545D53D?B@?G5B
24VDC @ 200mA Max. used for Special Application
(non-supervised, for supervision use PSR-2040)
>F9B?>=5>D1<?@5B1D9>7
3?>49D9?>C
Ambient temperatures: 32 - 120 degree F (0 - 49 degrees C)
Humidity: Max. 95% relative non-condensing
*Battery requirements calculated per individual system demands. (See battery selection data)
**240VAC 50/60 Hz 0.85amp maximum also available. Check installation wiring diagram (IWD).
,?<D175
24 V Full wave rectified (FWR) with battery standby.
EBB5>D
Two amps per circuit three amps maximum combined
Maximum two conductor copper feed cable resistance may not exceed 1 ohm (see below
1.4 Volts Maximum Line Loss
-
Maximum of 500’ (feet)
-
Maximum of 300’ (feet)
N-
Maximum of 200’ (feet)
Note: Notification Appliance Circuits current rating may be reduced depending on
each systems current requirements. Reference the installation wiring diagram (IWD)
for individual systems actual ratings. Reference DS-9066 for more information

Table of Contents