10
10.4Statusdisplay
GreenLED RedLED
Actuatornotcommissioned Off isflashingquickly
Normaloperation/actuatorrunning On Off
Normaloperation/actuatorstationary Off On
Manualmodeactive isflashingalternately isflashingalternately
Manualmode:Extendvalvestem Off isflashing
Manualmode:Retractvalvestem isflashing Off
Automaticcommissioningrunning On On
Automaticandmanualcommissioning
successful
isflashing7x–1.5secondsoff On
Automaticcommissioningfailed isflashingquickly On
Overvoltage isflashing1x–1.5secondsoff On
Undervoltage isflashing2x–1.5secondsoff On
Memoryerror isflashing3x–1.5secondsoff On
Setvalueerror(<1V,<2mA) isflashing4x–1.5secondsoff On
Torqueerror isflashing5x–1.5secondsoff On
Under‐/Overtemperature isflashing6x–1.5secondsoff On
10.5Automaticcommissioning
Ensuresecureconnectionbetweenvalveandactuator.
TostarttheautomaticcommissioningpushbuttonB2minimum7seconds.
‐ Option1:Ifadjusted“openwithforce–closewithforce”,theactuatorwilldrivetothefinalopenvalve
positionviaforce,andbacktothefinalclosedvalve
position.
‐ Option2:Ifadjusted“openwithcalibratedstroke”(20/30/40mm),theactuatorwillstorethelowerposition
andthestrokeiscalculatedaccordingtothesettings.Ifthepossibletravelissmallerthanthepresetstroke,
theoperatingstrokewillbeautomaticallyreducedtothemax.possibleresulting
value.
Aftersuccessfulcommissioning,thegreenLEDisflashing7times.
Function Action pushbuttonB1 PushbuttonB2 LEDsequence
Automatic
commissioning
StartPush7seconds BothLEDsareon
Commissioningfinished
GreenLEDisflashing7x
(ifcommissioningis
finished),
greenLEDisflashing
quickly
(ifcommissioning
failed)
Exit Push1x RedorgreenLEDison
Manual
commissioning
Activate Push7seconds
BothLEDsareflashing
alternately
Rectractvalvestem Push Green LEDisflashing
Extendvalvestem Push RedLEDisflashing
Start Push3seconds Push3seconds BothLEDsareon
Exit Push1x RedorgreenLEDison