1)
AfterchangingtheswitchesS2‐3,S2‐4andS2‐9performre‐calibrationtoactivatethenewoperatingmode.
10.2Operatingdirection
10.3Operatorpushbutton
S2Function
1 2 3
1)
4
1)
5 6
7 8 9
1)
10
Split‐rangelow:0‐5V/0‐10mA
On
Off On
Split‐rangelow:2‐6V/4‐12mA
Off
Off On
Cut‐offbyforceifvalvestemisinextendedposition On
Cut‐offbyforceifvalvestemisinretractedposition Off
ValvecurveLINEARsetvalue/position
Off
ValvecurveQUICKOPENINGsetvalue/position
On
Function Action pushbuttonB1 pushbuttonB2 LEDsequence
Manualoperation
Activate >Push3seconds
>Push3
seconds
BothLEDsareflashing
alternately
Retractvalvestem Push Green LEDisflashing
Extendvalvestem Push RedLEDisflashing
Stop
BothLEDsareflashing
alternately
Exit Push3seconds Push3seconds RedorgreenLEDison
Figure7:Operatingdirection
SE=SpringExtend:Extendactuatorstem/retractvalvestem
SR=S