PQube User Manual 2.1
Page 104 of 113
Min_Frequency_of_Interest_in_Percent_of_Nominal=A
UTO
Max_Frequency_of_Interest_in_Percent_of_Nominal=A
UTO
The AUTO values are determined by the
Underfrequency and Overfrequency thresholds.
Min_AN1_E_of_Interest_in_RMS_volts=AUTO
Max_AN1_E_of_Interest_in_RMS_volts=AUTO
The AUTO values are determined by the Dip and Swell
thresholds on Analog Channel 1.
Min_AN2_E_of_Interest_in_RMS_volts=AUTO
Max_AN2_E_of_Interest_in_RMS_volts=AUTO
The AUTO values are determined by the Dip and Swell
thresholds on Analog Channel 2.
Min_AN1_AN2_of_Interest_in_RMS_volts=AUTO
Max_AN1_AN2_of_Interest_in_RMS_volts=AUTO
The AUTO values are determined by the AN1-AN2 Dip
and Swell thresholds.
Min_Temperature_of_Interest_in_Degrees_C=0
Max_Temperature_of_Interest_in_Degrees_C=50
Set the minimum and maximum temperature for
viewing in Trends and Statistics recordings if the AUTO
setting does not provide a suitable graph.
Min_Humidity_of_Interest_in_%_RH=0
Max_Humidity_of_Interest_in_%_RH=100
Set the minimum and maximum relative humidity in %
for viewing in Trends and Statistics recordings.
Max_Voltage_Unbalance_of_Interest_in_Percent=10%
Set the full scale Voltage Unbalance in Trends and
Statistics recordings.
Max_Current_Unbalance_of_Interest_in_Percent=99%
Set the full scale Current Unbalance in Trends and
Statistics recordings.
Max_Voltage_THD_of_Interest_in_Percent=10%
Set the full scale THD voltage in Trends and Statistics
recordings.
Max_Current_TDD_of_Interest_in_Percent=25%
Set the full scale TDD current in Trends and Statistics
recordings.
Max_Flicker_of_Interest=4
Set the full scale RMS Flicker in Trends and
Statistics recordings.