PQube User Manual 2.1
Page 87 of 113
Analog_1_Channel_Name=”AN1-E”
Analog_1_Channel_Unit=”V”
Analog_2_Channel_Name=”AN2-E”
Analog_2_Channel_Unit=”V”
Use these tags to customize your channel names
and units.
Valid names can
be up to 5
characters.
Valid units are:
“V”, “A”, “W”,
“DEG”, “%”,
“NONE”
Analog_1_Channel_Name=”DCV”
Analog_1_Channel_Unit=”V”
Analog_2_Channel_Name=”DCI”
Analog_2_Channel_Unit=”A”
Configure Event Triggering
[Phase_To_Neutral_Events]
Phase_To_Neutral_Events=AUTO
Use the AUTO setting to let your PQube decide to
record Phase-Neutral events or not. If your Power
Configuration includes a Neutral conductor, your
PQube will record Phase-Neutral events.
Dip_Threshold_In_Percent=90.00
Swell_Threshold_In_Percent=110.00
Interruption_Threshold_In_Percent=10.00
Event_Hysteresis_In_Percent=2.00
Set thresholds for Voltage Dips, Swells, and
Interruptions.
Percent refers to Percent remaining of nominal
voltage.
Phase_To_Phase_Events=AUTO
Use the AUTO setting to let your PQube decide to
record Phase-Phase events or not. If your Power
Configuration includes multiple phases, your
PQube will record
Phase-Phase events.