PQube User Manual 2.1
Page 72 of 113
may experience delayed response times, ranging from a few seconds up to several minutes,
depending on which parameters are being recorded.
PQube Modbus Register Table
Firmware Version 2.0
Offset
Register
Format
Units
Comments
0-1
L1-E
Float
RMS
Volts
L1 to earth U
rms10/12
2-3
L2-E
Float
RMS
Volts
L2 to earth U
rms10/12
4-5
L3-E
Float
RMS
Volts
L3 to earth U
rms10/12
6-7
N-E
Float
RMS
Volts
Neutral to earth U
rms10/12
8-9
L1-N
Float
RMS
Volts
L1 to neutral U
rms10/12
10-11
L2-N
Float
RMS
Volts
L2 to neutral U
rms10/12
12-13
L3-N
Float
RMS
Volts
L3 to neutral U
rms10/12
14-15
L1-L2
Float
RMS
Volts
L1 to L2 U
rms10/12
16-17
L2-L3
Float
RMS
Volts
L2 to L3 U
rms10/12
18-19
L3-L1
Float
RMS
Volts
L3 to L1 U
rms10/12
20-21
AN1-E
Float
RMS
Volts
Analog 1 to Earth U
rms10/12
22-23
AN2-E
Float
RMS
Volts
Analog2 to Earth U
rms10/12
24-25
AN1-AN2
Float
RMS
Volts
Analog1 to Analog2 U
rms10/12
26-27
Frequency
Float
Hertz
28-29
L1 Current
Float
RMS
Amps
A
rms10/12
30-31
L2 Current
Float
RMS
Amps
A
rms10/12
32-33
L3 Current
Float
RMS
Amps
A
rms10/12
34-35
N Current
Float
RMS
Amps
Neutral current - A
rms10/12
36-37
Power (W)
Float
Watts
Also see 204-209
38-39
Apparent Power (VA)
Float
VA
Also see 210-215
40-41
Digital Input
Float
(none)
Usually 0 or 1; a fractional value
indicates duty cycle
42-43
Peak Current (1-cycle)
Float
RMS
Amps
A
rms10/12
See also registers 122-124:
44-45
Peak Current (1-minute)
Float
RMS
Amps
1-minute RMS average
See also registers 122-124
46-47
Peak Current (N-minute)
Float
RMS
Amps
N-minute RMS average
Typically N is 10 minutes or 15
minutes. See register 1024.
Also, see also registers 122-124
48-49
Peak Power (1-cycle)
Float
Watts
See also registers 125-127
50-51
Peak Power (1-minute)
Float
Watts
See also registers 125-127
52-53
Peak Power (N-minute)
Float
Watts
Typically N is 10 minutes or 15
minutes. See register 1024. Also, see
registers 125-127
54-55
Peak VA (1-cycle)
Float
VA
See also registers 128-130
56-57
Peak VA (1-minute)
Float
VA
See also registers 128-130
58-59
Peak VA (N-minute)
Float
VA
See registers 128-130. Typically N is
10 minutes or 15 minutes - see

Table of Contents