PQube User Manual 2.1
Page 36 of 113
NOTE: Under normal operation, your PQube will update all of its registers approximately once per
second. However, you may experience delayed response times while your PQube is generating
files for events and trends. These response times can range from a few seconds, up to several
minutes, depending on which parameters are being recorded.
For a description of the available registers, see Appendix 1 (page 71).
Simple Network Management Protocol (SNMP)
A beta version of SNMP is included in Firmware 2.0. SNMP is a common meter reading protocol
that is used in data centers worldwide. For easy SNMP installation, a PQube MIB file is included
with 1.4 release files.
Use the following information to connect to your PQube:
SNMP port: 161
Get community string: pqube
Set community string: pqube
For a description of the available values in the MIB file, see Appendix 4 (page 109).