PQube User Manual 2.1
Page 88 of 113
Dip_Threshold_In_Percent=90.00
Swell_Threshold_In_Percent=110.00
Interruption_Threshold_In_Percent=10.00
Event_Hysteresis_In_Percent=2.00
Set thresholds for Voltage Dips, Swells, and
Interruptions.
Percent refers to Percent remaining of nominal
voltage.
Trigger events for frequency.
Underfrequency_Threshold_In_Percent=99.50
Overfrequency_Threshold_In_Percent=100.50
Event_Hysteresis_In_Percent=0.20
Set thresholds for frequency event detection here.
[High_Frequency_Impulse_Events]
Set this tag to ON to begin recording transients or
high frequency impulses. The detection threshold
is 450V peak.
Your PQube can detect transients as short as 1
microsecond.
Waveform_Snapshot_Interval_In_Hours=24
Your PQube is scheduled to record a Snapshot of
your electric power at this interval.
When the interval is 24 hours, your PQube will
take a Snapshot of your power at 12 noon every
day.