PQube User Manual 2.1
Page 89 of 113
Waveform_Snapshot_At_Startup=OFF
Set this tag to ON to take a Snapshot of your
electric power every time your PQube is powered
on or reset.
Enable_Snapshot_Harmonics=ON
Set this tag to ON to include a harmonics spectrum
for voltage (and current, where applicable) when a
Snapshot is generated.
NOTE:
Your PQube’s sampling rate must be set to
128.
Set this tag to ON to enable event triggering on
your Analog channel 1.
Dip_Threshold_In_Volts=2.00
Swell_Threshold_In_Volts=60.00
Event_Hysteresis_In_Volts=0.5
Set event detection thresholds for Analog channel
1.
Set this tag to ON to enable event triggering on
your Analog channel 2.
Dip_Threshold_In_Volts=2.00
Swell_Threshold_In_Volts=60.00
Event_Hysteresis_In_Volts=0.5
Set event detection thresholds for Analog channel
2.