Setup.ini Tags
Comments
Valid Values
Example
[AN1_AN2_Events]
AN1_AN2_Events=OFF
Set this tag to ON to enable event triggering using
AN1 and AN2 differential voltage.
ON
OFF
USER_COUNTER
Dip_Threshold_In_Volts=2.00
Swell_Threshold_In_Volts=60.00
Event_Hysteresis_In_Volts=0.5
Set event detection thresholds for AN1-AN2
voltage.
[DIG1_Events]
Enable_DIG1_Dip_Event=OFF
Enable_DIG1_Swell_Event=OFF
Trigger events on the DIG1 channel. When
configuring the DIG1 events, take care not to
unintentionally get stuck in an infinite event.
ON
OFF
DIG1_Dip_Threshold=0.5
DIG1_Swell_Threshold=0.5
DIG1_Event_Hysteresis=0.1
[Phase_Current_Events]
Phase_Current_Events=OFF
Trigger events for current on L1, L2, and/or L3.
ON
OFF
Level_Threshold_In_Amps=AUTO
Level_Hysteresis_In_Amps=AUTO
Set the level threshold here. Your PQube will
record an event when the current exceeds this
level.
Inrush_Threshold_In_Amps=AUTO
Inrush_Threshold_In_Cycles=2
Set the inrush threshold here. Your PQube will
record an event when the current exceeds the
Inrush_Threshold_In_Amps value, for a period of
the Inrush_Threshold_In_Cycles or less.