[Adjust_Phase_Connections]
L1_Input_Connected_To=L1
L2_Input_Connected_To=L2
L3_Input_Connected_To=L3
N_Input_Connected_To=N
L1_Amps_Input_Connected_To=L1
L2_Amps_Input_Connected_To=L2
L3_Amps_Input_Connected_To=L3
N_Amps_Input_Connected_To=N
E_Amps_Input_Connected_To=E
Use this section to correct any installation errors
during installation.
L1_Input_Connected_To=L2
(This means the L1 screw
terminal is connected to the
L2 conductor.)
Enables AN1xAN2 channel for DC power and
energy measurements. Use with ATT2 module.
AN1-E_Channel_Ratio=1:1
AN2-E_Channel_Ratio=1:1
You can use fractional values.
Resistive_Attenuator_Correction=OFF
To increase accuracy, you should set this to ON if
you are using an optional external ATT1-600V or
ATT1-1200V module with your PQube’s AN1 and
AN2 screw terminals.
Analog_Measurement_Mode=DC_RMS
Increases accuracy by applying a small adjustment
factor that compensates for digital filtering.
Swap_AN1_And_AN2_Connections=OFF
Use this to fix an installation error on the Analog
channels.