PQube User Manual 2.1
Page 85 of 113
Potential_Transformer_Ratio=1:1
You can use fractional values such as 1250.5:120
L1_E_Voltage_Gain_Calibration_Factor=1.0000
L2_E_Voltage_Gain_Calibration_Factor=1.0000
L3_E_Voltage_Gain_Calibration_Factor=1.0000
N_E_Voltage_Gain_Calibration_Factor=1.0000
Set gain correction factor for mains voltage
terminals.
Current_Transformer_Ratio=1:1
Neutral_Current_Transformer_Ratio=1:1
Earth_Current_Transformer_Ratio=1:1
For voltage-input current modules, the second
number is the voltage.
You can use fractional values such as
100.35:0.333
Invert_L1_Current_Channel=OFF
Invert_L2_Current_Channel=OFF
Invert_L3_Current_Channel=OFF
Invert_N_Current_Channel=OFF
Invert_E_Current_Channel=OFF
If your CTs have been installed backwards, you
can reverse the polarity here.
Calculate_Current_Channel=OFF
If you have current transformers on all
conductors except one, your PQube can
calculate the remaining channel.