PART 1 – GENERAL
1.01 SCOPE
A. The requirements of the General Conditions, Supplementary Conditions, Division 1,
and Drawings apply to all Work herein.
B. Provide Microprocessor controlled, multiple-scroll compressor, air-cooled, liquid chill-
ers of the scheduled capacities as shown and indicated on the Drawings, including but
not limited to:
1. Chiller package
2. Electrical power and control connections
3. Chilled water connections
4. Change of refrigerant oil (for factory mounted evaporator) or (evaporator shipped
separatelyforeldinstallationandpipingbycontractor)
1.02 QUALITY ASSURANCE
A. ProductsshallbeDesigned,Tested,RatedandCertiedinaccordancewith,andin-
stalled in compliance with applicable sections of the following Standards and Codes:
1. ANSI/ASHRAE Standard 15 – Safety Code for Mechanical Refrigeration
2. ASHRAE90.1–EnergyEfciencycompliance.
3. ANSI/NFPA Standard 70 – National Electrical Code (N.E.C.).
4. ASME Boiler & Pressure Vessel Code, Section VIII, Division 1.
5. AHRI Standard 550/590 – Positive Displacement Compressors and Air Cooled Ro-
tary Screw Water-Chilling Packages.
6. Conform to Intertek Testing Services, formerly ETL, for construction of chillers and
provide ETL/cETL Listing label.
7. Manufactured in facility registered to ISO9002.
8. OSHA - Occupational Safety and Health Act
B. Factory Test: Chiller shall be pressure-tested, evacuated and fully charged with refrig-
erantandoil,andshallbefactoryoperationalruntestedwithwaterowingthroughthe
vessel.
C. Chiller manufacturer shall have a factory trained and supported service organization
that is within a 50 mile radius of the site.
D. Manufacturer shall Warrant all equipment and material of its manufacture against de-
fects in workmanship and material for a period of one year from date of initial start-up
oreighteen(18)monthsfromdateofshipment,whicheveroccursrst.
Guide Specifications