R2K 24 - RAD - ING - Inst.Manual - 2002.1_CSA
2. FIRST START-UP
PARAMETER DESCRIPTION RANGE FUNCTION
P10 DOMESTIC FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN DOMESTIC MODE. [SEE 2.1.6 ‘COMBUSTION BLOWER
FREQUENCY/HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
45 - VALUE
SET FOR
PARAMETER
P11
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P11 DOMESTIC FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE IN
DOMESTIC MODE [SEE 2.1.6 ‘COMBUSTION BLOWER FREQUENCY/
HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
V A L U E
SET FOR
PARAMETER
P10 - 203
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P12 HEATING FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE IN
HEATING MODE. [SEE 2.1.6 ‘COMBUSTION BLOWER FREQUENCY/
HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
45 - VALUE
SET FOR
PARAMETER
P13
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P13 HEATING FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE IN
HEATING MODE [SEE 2.1.6 ‘COMBUSTION BLOWER FREQUENCY/
HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
V A L U E
SET FOR
PARAMETER
P12 - 203
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P14 STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED
DURING START-UP.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
V A L U E
SET FOR
PARAMETER
P10 - 203
THE VALUE IS EXPRESSED IN
HERTZ (1HZ = 30 RPM) - (PRE-
SET AT 120 HZ)