R2K 24 - RAD - ING - Inst.Manual - 2002.1_CSA
2. FIRST START-UP
SUPPORT CENTER
2.1.5. DIGITECH CS (MIAH402) PARAMETERS TABLE
PARAMETER DESCRIPTION RANGE FUNCTION
P00 BOILER MODEL SELECTION 0 - 10 0 - 7 = N.A.
8 = R2K 24 - R2KA 24/8
9 = R2K 34 - R2KA 34/20 - R1K 34/B
10 = R1K 55-R2K 55
P01 BOILER TYPE SELECTION 0 - 5 0 = INSTANTANEOUS > R2K
1 = N.A.
2 = ACCUMULATION
(STORAGE)> R1K /B - R2KA
3 = ACCUMULATION (STORAGE)
COMFORT > R1K /B - R2KA
4 = INSTANTANEOUS COMFORT -
FAST H2O> R2K
5 = HEATING ONLY> R1K 55
P02 GAS TYPE SELECTION
ATTENTION:
READ THE INSTRUCTION IN 2.2.19 ‘CONVERSION TO A DIFFERENT
GAS TYPE’ BEFOR E CHANGING THIS PARAMETER.
0 - 1 0 = NATURAL GAS (AND SETS
FAN SPEED SETTING AT
PARAMETERS P10 - P11 - P12 -
P13)
1 = PROPANE (AND SETS
FAN SPEED SETTING AT
PARAMETERS P10 - P11 - P12 -
P13)
P03 SETTING THE HEATING TEMPERATURE
IN CASE THE BOILER IS INSTALLED AS PART OF A LOW
TEMPERATURE CIRCUIT, PLEASE INSTALL A SAFETY
THERMOSTAT ON THE HEATING FLOW, WHICH CAN STOP
THE BOILER ACTIVITY IN CASE OF HIGH HEATING FLOW
TEMPERATURE. THE COMPANY ASSUMES NO LIABILITY FOR
DAMAGE CAUSED TO PERSONS OR FOR FAILURE TO COMPLY
WITH THESE INSTRUCTIONS.
0 - 1 0 = STANDARD 86-167 °F (30-75
°C)
(SET BY DEFAULT)
1 = REDUCED 77-113 °F (25-45
°C) FOR FLOOR SYSTEMS