EasyManua.ls Logo

Rain Bird ESP-MC - Troubleshooting RASTER Valve Circuits (Continued); Diagnosing Short Valve Circuits; Troubleshooting Open;Short Circuit Issues

Rain Bird ESP-MC
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rain Bird RASTER
TM
(Rapid Station Test Routine), continued
12
Short Circuits
When the RASTER
TM
shows a SHORT test result, it
indicates an unintended re-routing of the current
flow somewhere between the controller and the
valve.
These are some of the most common causes of
short circuits:
A shorted valve solenoid
Nicked or skinned field wires
Loose or corroded wire connections on the
controllers terminal strip or at the valve solenoid
A malfunctioning component on the controllers
internal circuit board.
Troubleshooting Opens and Shorts
Use the following procedure to troubleshoot any
valve identified as OPEN or SHORT.
1. Make sure the problem valves station wires are
securely connected on the controllers terminal
strip.
2. If the wires were securely connected, move the
problem stations wires to a station that passed
the RASTER
TM
and re-start the test.
3. If the OPEN or SHORT moves to the new
station, check the problem valves solenoid and
field wiring.
4. If the OPEN or SHORT reoccurs on the
original station, the controllers internal circuitry
may need service.

Table of Contents

Other manuals for Rain Bird ESP-MC

Related product manuals