SECTION 6: LIFTING AN A IR HANDLER
13
6.1.3 Lifting an Upright Air Handler
All air handlers are shipped in the horizontal position.
Prior to lifting an upright air handler, the following
steps must be performed (See Page 13, Figure 4):
Step 1: The air handler must be lifted using the two
lifting lugs on the top of the discharge end and the
two lifting lugs on the inlet end, using a spreader bar
across the long axis. Lift the air handler off the skid
and place it on a flat, clean, dry surface.
Step 2: Remove the lifting lugs on the inlet end of the
air handler and re-install hardware.
Step 3: Use all four lifting lugs on the discharge end
of the air handler to enable the air handler to be lifted
into the upright position.
Step 4: Lift the air handler into upright position.
Step 5: Next, refer to the applicable portions of Page
18, Section 9 for specific mounting instructions.
FIGURE 4: Lifting an Upright Air Handler
Step 1
Remove These
Lifting Lugs
Step 2
Step 3
Step 4
Spreader Bar
INLET
INLET
INLET