EasyManua.ls Logo

Rapido F110 NT - Operation and Maintenance; Operation; Care and Maintenance; Flue Cleaning

Rapido F110 NT
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
f) Set storage charging pump switch (and circuit No. 2
heating pump, with SP 1.2) to
auto: if a rapidomatic S, 2 SM, 3 SM, Z 2.3 SM, Z 3.3
SM
heat regulator is in operation.
man: if running without rapidomatic heat circuit con-
trol, with incorrect working of control or when
running exclusively with RTU room dial
thermostat.
g) Set burners according to manufacturer’s instructions,
taking into account boiler capacity and the specified
combustion values.
h) Allow unit to heat up.
i) Check that all control, regulating and safety devices are
functioning properly and correctly adjusted.
j) If water level in unit is low, refill with water when boiler
has cooled down.
k) Train operator(s) in correct use of the unit.
10. Operation
See installation instructions for corresponding control pa
-
nel or regulator.
10.1 Taking out of service
Disconnect at main switch.
Shut off oil or gas supply.
10.2 Danger of frost damage
If heating operation is interrupted for long periods during
winter, the whole heating system including the boiler
must be completely emptied of water. Check when empty
-
ing that the drain tap does not become blocked with dirt.
The drain tap must remain open until the unit is refilled.
11. Care and maintenance
According to DIN 4755 and DIN 4756, all oil- or gas-fired
appliances must be inspected at least once a year for
correct and economical operation, and for safety, by a
person appointed by the system designer or other qualified
person. Combustion values are to be checked and, if
necessary, readjusted. It is advisable to take out a main-
tenance contract.
The boiler-room should be clean, dry and ventilated. The
boiler should be cleaned at certain intervals. Cleaning
regularity depends on fuel consumption, but should take
place at least at the start of each cold season.
11.1 Flue cleaning
Disconnect at main switch.
Remove front jacket.
Loosen nuts on burner door and lift door open.
Pull out radiation converter.
Clean combustion chamber and flue draughts with
a cleaning brush.
Fig. 15 cleaning boiler with a cleaning brush
Remove flue gas collector cleaning access cover and
cleanflue gas collector.
Replace cleaning access cover.
Clean remains of burnt fuel from boiler.
Replace radiation converter.
Fig. 16
The radiation converters are identified with numbers. This
identification number must face forwards when installing.
Insert radiation converters in flues according to identificati
-
on number as in Fig. 16.
NB!
The radiation converters are easily inserted. Do not
use undue force!
Note:
The number of radiation converters depends on boiler size
(see technical data table, chapter 7).
Flue baffle plates are installed with F 110/3 NT and F
110/4.1 NT only.
Some or all of the radiation converters can be removed for
purposes of controlling flue temperature with certain chim
-
ney configurations.
Shut burner door and tighten nuts.
Replace front jacket.
Reconnect at main switch and check combustion values.
Troubleshooting
17
F 110 NT front section
radiation converters
flue baffle plate
(F 110/3 + 4.1 NT only)

Table of Contents

Related product manuals