Power Meter Quick Setup Guid
e
-PMM-1A-v3.3.10-E 255-64-0004-00
Product Specification
Voltage Measurement Inputs:
Input Range* 90-277VLN, 156-480VLL
Phase to Ground* 277V
Measurement
Category
CAT III, Pollution Level 2
Frequency 47-63 Hz
Input Impedance 10MΩ
*Ratings for models with field wiring terminals. For models with factory
installed line-cords, rating is limited by plug and ratings are labeled on
back on unit.
Current Measurement Inputs:
Input Range 0-400mV
Input Impedance 10k
CT Type Voltage Output = 333mV at rated current
CT Rated Current 1-1200A
Meter Measurement Accuracy:
Active Power &
Energy
0.5%: IEC 62053 Class .5, EN 50470-3 Class C
Reactive Power &
Energy
2%