EasyManuals Logo

Raritan PMC-1000 Quick Setup Guide

Raritan PMC-1000
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
Power Meter Quick Setup Guid
e
4
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
RMS Voltage &
Current
0.2%
Frequency 0.1%
Sample Rate 64x AC frequency (phase locked)
Measurement
Update Rate
3 seconds: IEC 61000-4-30 Class S
Power Requirements:
Voltage 90-240V
Current 0.2A
Overvoltage
Category
CAT III, Pollution Level 2
Frequency 47-63 Hz
Mechanical:
Terminal Block Screw
Torque
0.37 ft-lb (0.5Nm) to 0.44 ft-lb (0.6Nm)
Terminal Block Wire
Size
14-24AWG (.5-1.6mm)
Terminal Wire
Temperature Rating
> 75 degree C
DIN Rail T35 (35mm)
Environmental:
Operating Temperature 0-60°C
Operating Humidity 5-85%RH
Operating Elevation 0-3000m
Conformance:
Safety UL/EN 61010-1
EMC/EMI EN61326-1, FCC Part 15 Class A

Other manuals for Raritan PMC-1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raritan PMC-1000 and is the answer not in the manual?

Raritan PMC-1000 Specifications

General IconGeneral
BrandRaritan
ModelPMC-1000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals