SmartRescue Specications
Conforms to UL STD 2017
Type of Signaling:
• Emergency Signaling, TYPE AM
Protection:
• Short Circuit/Overload/Over Voltage
Ratings for SmartRescue Base Stations:
• Input Ratings: 100-120vac, 50/60Hz, 4.0A or 200-240vac, 50/60Hz, 2.0A when powered by 2500-PWR24U
• Output Rating: 24vdc, 5A
• Input Ratings: 100-240vac, 50/60Hz, 0.7A when powered by RP7300061
• Output Rating: 24vdc, 1.1A
• Input Ratings: 100-240vac, 50/60Hz, 0.65A when powered by RP7300055
• Output Rating: 24vdc, 1.04A
Ratings for 2100 Series SmartPhones:
• 24vdc, 0.5A when powered by 2500-PWR24U
• 24vac, 5VA when powered by RP7300110
Environmental:
• For indoor use only
• Operating temperature 32° F to 120° F (0° C to 49° C)
TB1 Relay:
• Load Current: 130mA
• Load Voltage: 350vdc or vac
Note: Input power circuit, battery circuit, and phone circuits are supervised in accordance with UL 2017 Section 84.3.
Rechargeable Battery Ratings:
SmartPhone
• Voltage: 7.2V
• Max Circuit Current: 80mA
Amp Hour Capacity: 1300mAh
• Expected Standby Time: 24 hours
• Replacement Part: RP7300110
SmartRescue
• Voltage: 16.8V
• Max Circuit Current: 100mA
Amp Hour Capacity: 1400mAh
• Expected Standby Time: 24 hours
• Replacement Part: RP7300109A
Model Number 5 Zone 10 Zone Stainless Steel
Enclosure
Powder Coated
Steel Enclosure
Surface Mount Flush Mount
2500-205D X X X
2500-210D X X X
2500-205PSS X X X
2500-210PSS X X X
2500-205B X X X
2500-210B X X X
2500-205FM X X X
2500-210FM X X X