6 | Electrical connection
80.06.231_iVarioProL-iVarioProXL_IM_en-GB 43 / 72
n
Calculate the conductor cross section according to the length and quality
of the power cable used.
3 NAC 400 V Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 27 40 40 6
iVario Pro XL 41 59 63 10
3 NAC 400 V
Balanced power
Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 21 30 32 4
iVario Pro XL 34 50 50 10
3 NAC 415 V Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 29 41 50 10
iVario Pro XL 44 61 63 10
3 AC 200 V Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 26 74 80 16
iVario Pro XL 38 111 125 35
3 AC 208 V Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 23 64 70 16
iVario Pro XL 34 96 100 25
3 AC 220 V Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 25 66 80 16
iVario Pro XL 38 100 100 25
3 AC 230 V Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 27 69 80 16
iVario Pro XL 41 103 125 35
3 AC 240 V Power kW Amp draw A Fuse A Conductor cross-sec-
tion mm²
iVario Pro L 22 53 60 10
iVario Pro XL 37 88 100 25