EasyManua.ls Logo

Reflex Fillcontrol Auto Series - Technical Data; Electrical System Specifications; Dimensions and Connections; Operational Parameters

Reflex Fillcontrol Auto Series
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
16
English Fillcontrol Auto Make-up and degassing06.07.2016 - Rev. B
5 Technical data
Note!
The following values
apply for all systems:
Permissible ambient temperature:
Degree of protection:
Noise level:
>0 °C 45 °C
IP 54
55 dB
5.1 Electrical system
Type
Power output
(W)
Power supply
(V / Hz)
Fusing
(A)
Number of RS-485
interfaces
I/O module
Fillcontrol Auto 2P 500 230 / 50 10 2 Optional
Fillcontrol Auto 2PS 500 230 / 50 10 2 Optional
5.2 Dimensions and connections
Type
Weight
(kg)
Height
(mm)
Width
(mm)
Depth
(mm)
Device
connection
System
connection
Overflow
connection
Fillcontrol Auto 2P 47 930 500 560 RP ½ G 1
Fillcontrol Auto 2PS 55 1030 500 580 RP ½ G 1
5.3 Operation
Type
Make-up capacity
(l/h)
Maximum feed
pressure
(bar)
Maximum delivery
pressure
(bar)
Permissible operating
gauge pressure
(bar)
Operating
temperature
(°C)
Fillcontrol Auto 2P
4200
10
8.5
6 70
Fillcontrol Auto 2PS
4200
10
8.5
6 70

Table of Contents

Related product manuals