Controller
44
— English Fillcontrol Auto Make-up and degassing06.07.2016 - Rev. B
9.2.2 Service menu
The Service menu is password-protected. Only Reflex service technicians are able to access this menu, see chapter 12.1 "Reflex Customer
Service" on page 53 .
Parameter
Setting
Remarks
Pressurisation
Pump "ON" P
0
+ 0.3 bar
Differential pressured added to the "P
0
" minimum operating
pressure
Pump "OFF" P
0
+ 0.4 bar
Differential pressured added to the "P
0
" minimum operating
pressure
Forced start of the pumps 24 h
If the pumps are standing still for 24 hours, they are forced to run
for 3 seconds
"Pump run time exceeded" message 30 minutes The message is displayed after the pumps run for 30 minutes
Maximum pressure 6 bar
Degassing, active only in Fillcontrol Auto 2PS
Degassing P
0
+ 0.4 bar
Differential pressured added to the "P
0
" minimum operating
pressure
Degassing time of interval degassing mode 90 seconds
Idling time of interval degassing mode 120 minutes
Interval degassing start 08:00 h
Interval degassing end 18:00 h