Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B English —
Note!
The following settings apply to Fillcontrol Auto 2P and Fillcontrol Auto 2PS.
-up" sub-menu. Make-up
Switch to the next list item.
Make-up
-up cycle. Upon expiry of the set time, the system interrupts the
-up and returns the "Make-up time" fault message.
Max. make-up time
If the set number of make
-up cycles is exceeded within 2 hours, the system interrupts the
-up and returns the "Make-up cycles" fault message.
Max. make-up cycl.
Kontaktwasserzähler FQIRA+ ist installiert, see chapter 4.6 "Optional equipment and
accessories" on page 15 .
This is a prerequisite for make-up quantity monitoring.
With water meter
A contact water meter is not installed (standard).
"YES" has been set in the "With water meter" menu option.
Make-up quantity
Delete meter:
The displayed make-up quantity is set to 0.
The displayed water quantity is retained.
Only displayed if "YES" has been set in the
"With water meter" menu option.
When the set quantity is exceeded, the system interrupts the make
-up process and returns
the error message "Max. make
-up quantity exceeded".
Max. make-up qty.
Recommended maintenance message.
Next maintenance
Without maintenance recommendation.
– 060: Maintenance recommendation in months.
Ausgabe von Meldungen auf den potenzialfreien Störkontakt, see chapter
9.3 "Messages"
45 .
Floating contact
Output of all messages.
Output of all messages identified with "xxx" ("01", for example).
Acoustic signal (horn) at fault contact
Horn at fault contact
Acoustic signal is output with the fault contact
No acoustic signal with fault contact
Use "Quit" (acknowledge) to deactivate the acoustic signal for the fault contact.