Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B English —
31 EEPROM defective Yes • EEPROM defective
• Internal calculation error
Contact the Reflex Customer
Service
Quit
32 Undervoltage Yes Supply voltage not achieved Check power supply -
33
Adjustment
parameter faulty
-
EPROM parameter memory
defective
Contact the Reflex Customer
Service
Quit
34
Main board
communication
faulty
- • Connecting cable defective
• Main circuit board defective
Contact the Reflex Customer
Service
Quit
35
Digital input voltage
faulty
- Short-circuit of input voltage
Check the wiring at the
digital inputs (water meter,
for example)
-
36
Analogue input
voltage faulty
- Short-circuit of input voltage
Check the wiring at the
analogue inputs
(pressure/level)
-
37
No input voltage for
the 3-ways motor
ball valve
- Short-circuit of input voltage
Check the wiring of the
motor ball valve
-