Operation
Vacuum spray degassing28.08.2019 - Rev. B
English23
8 Operation
8.1 Operating modes
8.1.1 Automatic mode
Automatic mode includes the two operating modes continuous degassing and interval degassing.
Note!
The starting time of the degassing
processes is specified based on the initial commissioning time.
To reset and for new setting of the start times, see chapter 9.5 "Reset" on page 27
Continuous degassing
This mode is started during first commissioning by pressing the Auto button. Multiple degassing cycles without pause times are
carried out over a fixed period of several hours during the day. The daily start time is set based on the time of the initial
commissioning.
Once continuous degassing has completed, interval degassing starts automatically.
Interval degassing
This mode comprises repeating intervals. There is an idling time between the intervals.
8.1.2 Stop mode
On the controller, press ‘Stop’ to activate stop mode. The Auto LED of the operating panel goes out, the Stop LED lights up.
Function monitoring is not performed in stop mode. The pump is switched off.
Note!
If stop operation is activated for longer than 4 hours, an error message appears on the device to signal an
uncontrolled
deactivation. This is also indicated in the app Reflex Control Smart.
8.1.3 Restarting
Note!
Recommissioning after a long shut
-down takes place by pressing the ‘Auto’ button.
9 Controller
9.1 Reflex Control Smart
Access to the Servitec S is possible using the Reflex Control Smart app via a Bluetooth-connected smartphone or tablet. The app is
available from the app store (Android or iOS), or via the QR code given below.