48
Manual CORRIGO C-SERIES 2000.09
CONFIGURATION- Corrigo C10 A B C D . E F G H . I J K L
Configuration code 1 . .
A Control function
0. Supply air control 0
1. Supply air control with outdoor temperature compensation 1
2. Room control with cascaded supply air temperature control 2
3. Room control with min/max limiting of supply air temp. 3
4. Room control, single sensor 4
5. Supply air control/Room control. Outdoor temp dependent 5
6. Exhaust air control with min/max limit of supply air temp 6
B Heater type
0. Water heater 0
1. Electric heater 1
C Output Y1
0. Not active 0
1. Heating 1
2. Damper 2
3. Cooling 3
D Output Y2
0. Not active 0
1. Plate heat exchanger 1
2. Rotating heat exchanger 2
3. Liquid connected heat exchanger 3
4. Damper 4
5. Heating 5
6. Cooling 6
E Output Y3
0. Not active 0
1. Cooling 1
2. Heating 2
F Frost protection (Water heating only)
0. Not active 0
1. Active on Y1 1
2. Active on Y2 2
3. Active on Y1 with automatic alarm reset 3
4. Active on Y2 with automatic alarm reset 4
G Shutdown mode (Water heating only)
0. No 0
1. Yes 1
H Pump stop (Water heating only. Requires outdoor sensor)
0. No 0
1. Yes 1
I Efficiency monitoring
0. No 0
1. Yes 1
J DX-cooling
0. No 0
1. 1-step 1
2. 2-step 2
3. 3-step binary 3
K Cooling recovery
0. No 0
1. Yes 1
L Free cooling
0. No 0
1. Yes 1