Why does my REMEHA Boiler show a 5x Error of unintended Flame Loss occurrence?
- DDavid CollierAug 26, 2025
If your REMEHA Boiler shows a 5x Error of unintended Flame Loss occurrence, it could be due to: * Low ionization current: Vent the gas supply to remove air. * Gas valve issues: Ensure the gas valve is fully opened and check its operation and setting. * Gas supply problems: Check the gas supply pressure. * Blockages: Verify that the air supply inlet and flue gas outlet are not blocked. * Flue gas recirculation: Ensure there is no recirculation of flue gases.