Why Return temperature is higher than flow temperature in REMEHA Quinta Ace Boiler?
- RrvargasSep 12, 2025
If the return temperature sensor has a higher temperature value than the flow temperature in your REMEHA Boiler, check the wiring and connectors. Also check the circulation (direction, pump, valves), ensure the sensor has been correctly fitted, check the Ohmic value of the sensor, and replace the sensor.