What causes REMEHA Quinta Pro 115 Boiler temperature of heat exchanger to be too low?
- BblakejasonAug 28, 2025
If the temperature of the heat exchanger in your REMEHA boiler is too low, it could be due to a bad connection, the sensor not being connected correctly, or no circulation. Check that the sensors are operating correctly, and that the sensor has been fitted properly. If necessary, replace the sensor. Vent the air from the CH system, check the circulation (direction, pump, valves), the water pressure, and the cleanliness of the heat exchanger. If present, check the boiler type parameter setting.