Fault EC: No cooling performance or heating performance after 30 minutes
Switch the unit off for 5 seconds. Is the fault still
shown on the display?
Is the indoor unit blowing out cold air or warm
air?
Check the probe on the evaporator (T2). Is this
correctly seated?
Check all pipe connections for leak-tightness. Is
there a deficit of refrigerant?
Replace the indoor unit circuit board.
Rectify the leak and fill with new refrigerant.
Are the pipelines kinked or perhaps contami-
nated?
Replace the pipelines.
Fault P0: Inverter module fault
Check the electrical wiring between the circuit
board and the compressor. Is this correctly
implemented?
Replace the connections.
Check whether the IPM module is correctly
installed.
Correct the installation and retighten all
screwed connections.
Does the condenser fan run properly?
Check the connection of the condenser fan
motor or replace it if necessary.
Replace the outdoor unit motherboard. Is the
fault still present?
Replace the compressor.