4 Commissioning
scrolling downwards (-)
scrolling upwards (+)
(selection / adjustment mode)
Î Connect the device to the mains.
The controller runs an initialisation phase.
When the controller is commissioned or when it is reset, it will run a commission-
ing menu. The commissioning menu leads the user through the most important
adjustment channels needed for operating the system.
1. Language
Î Adjust the desired menu language.
LANG
Language selection
Selection: dE, En, Fr, ES, It
Factory setting: dE
2. Temperature unit
Î Adjust the desired unit.
UNIT
Temperature unit
Selection: °F, °C
Factory setting: °C
3. Time
Î Adjust the clock time.
First of all adjust the hours, then the minutes.
TIME
Real time clock
4. Maximum store temperature
Î Adjust the desired maximum store temperature.
S MX
Maximum store temperature
Adjustment range: 4 … 95 °C [40 … 200 °F]
Factory setting: 60 °C [140 °F]
Note:
The controller is also equipped with a non-ad-
justable emergency shutdown, deactivating
the system if the store reaches 95 °C [200 °F].
Commissioning
adjustment mode ashing
Operation
changing a value ashing
conrming a value not ashing
to the next
parameter