6.5 After-heating of the boiler by buffer store:
The controller(1) measures the temperature difference
between buffer store sensorS1 and store sensor S2. As soon
as the difference is higher or identical to the adjusted value
(DO), the pump (3) is activated and the store is loaded up.
If the switch-off difference (DF) is underrun by the measured
difference, the pump is again deactivated.
The 3rd temperature sensor S3 is an additional sensor for
measuring purpose, e.g. for measuring the upper store
temperature.
6.6 Swimming pool solar system:
The controller (1) measures the temperature difference
between collector sensor S1 and swimming pool reverse
sensor S2. As soon as the difference is higher or identical
to the adjusted value (DO), the pump (3) is activated so that
the water in the pool is heated up. If the switch-off
difference (DF) is underrun by the measured difference, the
pump is again deactivated.
The 3rd temperature sensor S3 is an additional sensor for
measuring purpose, e.g. for measuring the upper store
temperature.