6.7 Thermostat after-heating function (only PG 53.02):
The third temperature sensor S3 can be used for the
thermostat function. The thermostat switch-on
temperature TO and the thermostat switch-off temperature
TF must be adjusted in the adjustment channels. Depending
on the adjustment, the thermostat function works in after-
heating or cooling operation.
to = 40 °C, tf = 40 °C
• to = tf
the thermostat function is deactivated, that means
that relay output R2 is activated if the maximum store
temperature is exceeded
• To < Tf
the thermostat function is used as after-heating
• To > Tf
the thermostat function is used as surplus energy