InstallationIndications, functions and optionsMessages Commissioning Operation and function
19
PRS 17
PUSH
OLEAK
Low pressure monitoring option
Adjustment range: OFF / ON
Factory setting: OFF
LEAKO
On at
Adjustment range: 0.3 5.7 bar
Factory setting: 0.7 bar
LEAKF
Off at
Adjustment range: 0.6 6.0 bar
Factory setting: 1.0 bar
DATE 18
PUSH
TIME
Time
Adjustment range: 00:00 … 23:59
Factory setting: 12:00
MM
Month
Adjustment range: 01 … 12
Factory setting: 03
YYYY
Year
Adjustment range: 2010 … 2099
Factory setting: 2010
DD
Day
Adjustment range: 01 … 31
Factory setting: 15
18
Time and date
The controller is equipped with a real time clock required e. g. for the thermostat
function.
18
17
Low pressure (leakage)
If the system pressure falls below the adjustable switch-on value, an error message
will appear.
When the pressure reaches or exceeds the adjustable switch-off value, the mes-
sage disappears.
Note:
For the Low pressure monitoring function, the switch-off value has to
be adjusted at least 0.1 bar higher than the switch-on value. The adjust-
ment ranges will automatically adapt to that.