Installation
CommissioningSettingsTroubleshooting
Accessories
Display
RPH sensor
Selection: S2, S3
Factory setting: S3
Thermostat function
(in systems 3 and 7 only)
Therm. on:
Thermostat switch-on temperature
Adjustment range: 0.0 ... 95.0 °C
Factory setting: 40.0 °C
Therm. off:
Thermostat switch-off temperature
Adjustment range: 0.0 ... 95.0 °C
Factory setting: 45.0 °C
Switch-on time 1 (2, 3):
Thermostat switch-on time
Adjustment range: 00:00 ... 23:59
Factory setting:
Switch-on time 1: 06:00
Switch-on time 2: 12:00
Switch-on time 3: 18:00
Switch-off time 1 (2, 3)
Thermostat switch-off time
Adjustment range: 00:00 ... 23:59
Factory setting:
Switch-off time 1: 07:00
Switch-off time 2: 13:00
Switch-off time 3: 20:00
The thermostat function can e. g. be used for using surplus energy or for afterheating.
Therm. on < Therm. off
thermostat function used for afterheating
Therm. on > Therm. off
thermostat function used for using surplus energy
In order to block the thermostat function for a certain period, there are 3 time
frames. If the thermostat function is supposed to run from 06:00 a.m. and 09:00
a.m. only, adjust the switch-on time 1 to 06:00 a.m. and the switch-off time 1
to 09:00 a.m.