Form CP-MAPS-D12 with FX05, Page 2
START
Unit On/OFF
Switch
Mode Controlled by:
Internal Time Clock or
Occ/Unocc Switch
Blower: Intermittent
ON call for space H or C
OR Space Humidity
Control
Space Heating
Setpoints
SSP - Hso - SHP - nSb
= 59.2°F
Discharge Air Setpoint
rHP = 80°F
Blower: Continuous
Damper 100% Open or
Other Control
Heat or Cool Neutral Air
Discharge Air Setpoint
dHL, dCH = 70°F
Heating Neutral Air
Discharge Air
Setpoint
dHL = 70°F
Space Heating
SSP - Hso -
SHP = 68.2°F
Discharge Air
Setpoint
rHP = 80°F
Dehumidification
Allowed
Enable dP1 = 60°F
Space Humidistat Switch
Closed; High and Low
Ambient Lockout
Heating Or Cooling Mode
Cooling, oAt > 68 °F (oC1)
Heating, oAt < 62 °F (oH1)
Occupied
Mode:
Unoccupied
Mode:
Damper(s): Open or
Other Control
Discharge Air setpoint
Space Heating
Space Cooling
Neutral Air
Heating
Space Cooling
SSP + SCP =
76.8°F
Discharge Air
Setpoint
rCP = 55°F
Cooling Neutral
Air
Discharge Air
Setpoint
dCH = 70°F
Discharge Air setpoint
Space Cooling
Neutral Air
Space Cooling
SSP + SCP =
76.8°F
Discharge Air
Setpoint
rCP = 55°F
Dehumidification
Not Allowed
Cooling
Heating Or Cooling Mode
Cooling, oAt > 68 °F (oC1)
Heating, oAt < 62 °F (oH1)
Space Humidistat Switch Closed
Space Cooling
Setpoints
SSP + SCP + nSu =
85.8°F
Discharge Air Setpoint
rCP = 55°F
Dehumidification
Allowed
Enable dP1 = 60°F
And RHE = Enable
Space Humidistat
Switch Closed
Dehumidification
Not Allowed
temperature, outdoor air temperature, dewpoint, and enthalpy. When equipped
with a wall-mounted sensor, space temperature will be displayed.
FIGURE 1 -
Sequence of
Operation with
Default Settings
Introduction (cont’d)
General Sequence
of Operation
When the unit is called to operate, the main blower will run continuously in
occupied mode and intermittently in unoccupied mode. The unit operates
based on four Discharge Air Temperature Setpoints listed below.
1. Standard (Neutral) Heating Discharge Air Temperature Setpoint
2. Space Heating Discharge Air Temperature Setpoint
3. Standard (Neutral) Cooling Discharge Air Temperature Setpoint
4. Space Cooling Discharge Air Temperature Setpoint
The heating and cooling equipment will cycle to maintain the active discharge
air temperature setpoint for occupied and unoccupied modes. Heating and
cooling may be locked out of operation based upon outdoor air temperature
and enthalpy conditions.
If equipped with reheat, the control will also activate the dehumidication circuit
to maintain a neutral discharge air temperature setpoint and related dewpoint
based upon outdoor air and space conditions.