EasyManuals Logo

Reznor RCB User Manual

Reznor RCB
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Form CP-MAPSIII-D21, Doc No 303070, Page 11
Space Cooling Inactive = Space dehumidication Y5 Reheat_Mod_Capacity and
NO17 Reheat Compressor Command permitted. If the Space Cooling is inactive and
thespacehumidityisabovethespacedehumidicationsetpoint,theunitwillenterthe
space dehumidication mode. While in the space dehumidication mode, the main
cooling compressors will be enabled to maintain a 52°F(11°C) cooling coil discharge
setpoint and will use the U5 CC_Temp sensor.
See dehumidication commands section for details on the operation of the reheat
compressorandmodulatingvalveY5outputinspacedehumidicationmode.
The unit will use the U4 DAT input and cooling demand to achieve the neutral discharge
air temperature setpoint.
A call for mechanical cooling will occur when the discharge air temperature is 5°F(2.8°C)
above the neutral air setpoint. When the OAT is above 65°F/18°C (Cooling Lockout
SP), the unit enables the mechanical cooling to maintain the neutral air setpoint. Cool-
ing capacity/staging will follow a PI loop to maintain the active setpoint.
When the OA dewpoint is greater than 58°F(14°C) the unit will enter the neutral air
dehumidicationmode.Whileintheneutralairdehumidicationmode,themaincool-
ing compressors will be enabled to maintain a 52
°F(11°C) cooling coil discharge set-
pointandwillusetheU5CC_Tempsensor.Seedehumidicationcommandssection
for details on the operation of the reheat compressor and modulating valve Y5 output
inneutralairdehumidicationmode.
3.7.1 Occupied Space Temperature Control and Setpoint
DX Mechanical Cooling Staging
PI Loop Control: All Statements Must Be True To Activate or De-Activate
All stages will have an adjustable min ON and OFF time
Stage Output
Increase
Stage Timing
Activate
Decrease
Stage Timing
De-activate
Stg 1 NO2 5 min DAT 5°F(2.8°C) above setpoint 5 min
Cooling Demand < 10 % & DAT
5°F(2.8°C) below setpoint
Stg 2 NO3 5 min
Cooling Demand > 70% & DAT
5°F(2.8°C) above setpoint
5 min
Cooling Demand < 50% & DAT
5°F(2.8°C) below setpoint
Stg 3 NO4 5 min
Cooling Demand > 80% & DAT
5°F(2.8°C) above setpoint
5 min
Cooling Demand < 55% & DAT
5°F(2.8°C) below setpoint
Stg 4 NO5 5 min
Cooling Demand > 90% & DAT
5°F(2.8°C) above setpoint
5 min
Cooling Demand < 60% & DAT
5°F(2.8°C) below setpoint
All parameters are factory level access.
3.6 Dehumidication
Dehumidication Commands
Wheneitherthespacedehumidicationmodeortheneutralairdehumidicationmode
are active, the main evaporator compressor(s) will be enabled to maintain a 52°F(11°C)
cooling coil discharge setpoint and will use the U5 CC_Temp sensor. The reheat com-
pressor and the reheat valve output Y5 will be enabled to modulate to maintain the
reheat setpoint 70°F(21°C) via the U4 DAT temp sensor.
Any of the following conditions will lockout the space dehumidication Mode:
1. The outdoor air temperature is below the reheat lockout setpoint, (58°F/14°C,
reheat lockout, range 50-100°F/10-37°C) Drybulb.
2. The outdoor air temperature is above the reheat high lockout setpoint.
(100°F/37°C, reheat high lockout, range 50-120°F/10-48°C) Drybulb
3. The space cooling mode is active.
4. Cooling Coil Sensor failure.
Any of the following conditions will lockout the neutral air dehumidication Mode:
1. The outdoor air temperature is below the reheat lockout setpoint, (58°F/14°C,
reheat lockout, range 50-100°F/10-37°C) Drybulb
2. The outdoor air temperature is above the reheat high lockout setpoint.
(100°F/37°C), reheat high lockout, range 50-120°F/10-48°C) Drybulb
3. Outside Air Humidity Sensor or Cooling Coil Sensor failure.
4. OA dewpoint less than 58°F(14°C).
3.5.2 Cooling Staging
Control Y3 (with
the Option CL78
th-tune device
DISABLED and NOT
COMMUNICATING)
3.5.1 Cooling Staging
Control Y3 (with the
Option CL78 th-tune
device ENABLED and
COMMUNICATING)
(Cont’d)

Other manuals for Reznor RCB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reznor RCB and is the answer not in the manual?

Reznor RCB Specifications

General IconGeneral
BrandReznor
ModelRCB
CategoryAir Handlers
LanguageEnglish

Related product manuals